20080316 1-st draft A. Blecha
20140325 graph 2008-2014 added AB
back to the main document
Message to the author
Content
Summary
Introduction
Measured COP
Measured input power
Extreme conditions
Practical considerations
Measurements 2008-2014
Summary
I report the first partial results (from October 26 to March 12) of the measurement campaign on the air-air heat pump (HP) installation in a
small, well insulated (specific loss 120 watt/degree), permanently inhabited house
located at the altitude of 600 m in the Lemanic region of the "Plateau Suisse". The house is 50 years old and was recently insulated according
the "best effort" strategy with moderate cost. A smallest Daikin HP is heating the surface of 64 m2 and power input, external
and internal temperatures are sampled every 5 minutes. The average coefficient of performance (COP) is 4.4 and the Seasonal Performance Factor (SPF) is 3.84
in excellent agreement with 3.9-4.1 predicted from the house thermal analysis and climatic data. Through the detailed analysis of the HP regulation we
conclude that a new economy mode preventing the HP to switch to the high-power regime when not necessary could improve the SPF by some 4%.
The measured vertical temperature profile of the heated area
is almost constant with a negligible peak-to-peak variation of 0.9 degree providing an unequaled comfort (fresh floor) and
contrasting with 4-5 degrees measured with electrical convectors. The air-air heat pump thus appears not only as the most economic solution
(this fact was established by several studies, see for example fig. 3 at page 3)
but also very comfortable and efficient solution well adapted to the "Plateau Swiss". For refitted old houses with no central heating installed,
the cost of air-air solution is several times lower then the brine/water (with earth heat source) solution heavily promoted in Switzerland.
Introduction
back to the content table
This is my private report on measurement carried out at Gingins during the season 2007-2008 after the installation of the Daikin Ururu Sarara FTXR28EV air-air heat pump (HP).
The purpose of this document is to demonstrate the efficiency of the installation for the heating in the geographic area of the Plateau Suisse and show the advantages
and drawbacks of such system.
I installed 2 smallest Daikin HP rather then split system to have the better efficiency and some redundancy (security). The first HP, subject to the measurements, is heating 64 m2 surface while the second one is heating another 16 m2 and could be used
as the back-up system. In the following we describe the measurement done on the main system though both pumps are fitted with
input power counter which records the total input energy and minimum/maximum input power for the whole period.
The instantaneous input current and external unit input temperature of the air are sampled every 5 minutes.
I have also some measurement of
the air temperature on the (compressor) external unit output. Actually the measurements cover the period of 137 days from 26 October 2007 to 12 of March 2008 with some
days without measurements so as the total number of days is 114 and 32'000 measurements. Total input energy for this period is 1500 kWh.
The internal unit is installed 70 cm above the floor and the distance between the internal and external unit is 7m.
Measured COP and SPF
back to the content table
The average COP over the period is 4.44 and the Seasonal Performance Factor (SPF) is 3.84. These are obtained as ratio between the
heat requirement computed from measured external temperature and house thermal model, and measured input energy.
All measurement available for the period 2007-2014

Note the drop of the input power (black) during the defrosting sequence as well as the simultaneous increase in the input temperature (mainly due
to the temperature sensor location on the input grid of the external unit). Note also the rather high input power used after the defrosting.

Note the very high input power used in the period 6-9h.
Measured input power
back to the content table
The histogram of the Total input energy per day
shows that during the heating season most of the time the required energy is below 12 [kWh] which leads
to the average input power of 0.5 [kW]. This is well under the nominal input power of 0.7 [kW] and if evenly distributed would be
in the range of the best efficiency of the HP.
However, the HP regime is far from "smooth". When looking at
the graphic of a typical day 20080310 with total energy input 12 [kWh] we notice that the
HP is either switching between high and low power (5-10h and 18-21h) or sort-off cycling between low and high level (21-24h). |

|

This is also visible on the histogram of all (32 000) measurements. Peaks at 300,800 and 1200 Watts indicate that
the HP has 3 stable regimes and switches between them according to the power requirement. Note that the
effect is smoothed by the fact that input power of each stable regime is temperature-dependent. The sum under the 1-st peak represents
66 % of all measurements and confirm that most of the time the HP is working close to the optimal power conditions.
There seems to be a possibility to slightly increase the overall efficiency of the HP by introducing
the "economy" mode where the high-power, less efficient regime is inhibited. In most situations the user will merely want
to increase the reference temperature but do not care how fast this temperature is reached.
According to our measurement, the average
COP could thus be improved by 2-3% and SPF by 4%. It is not much, but will only require small modification in Daikin control program.
|

|
Extreme conditions
back to the content table
When installing air-air or air/water heat pump, the first question which arises is how it will behave at low temperature. Daikin gives -15 as operational limit
but does not provide the correspondent COP at such temperature. If we base our estimate on Toshiba curves
we have respectively 66%,58% and 42% of the nominal output power at -5,-10 and -15. That gives the nominal output power for Daikin
2.4,2.1 and 1.5 [kW] respectively and maximal output power somewhere below 3.3,2.9,2.1 [kW]. During the coldest period,
in order to maintain the temperature of Tc=16 degrees
(house was unused and was heated continuously), we measured the average input of 1 [kW] at average input temperature Ti=-8. The required output energy being (Tc-Ti)*0.12[kW]=2.75[kW] the numbers
given by Toshiba seems to represent correctly the situation. Similar agreement is obtained for another cold period with Ti=-4 and Tc=21 where average input power was 0.8 [kW] and
required heat output of 3kW. I can draw at least 2 conclusions:
The nominal maximum input being 1.4 [kW] we have a considerable safety margin at the average temperature of -8.
Our COP power factor (we used a simple linear interpolation on min/nominal/max values given by Daikin) is slightly pessimistic.
In approximately 1% of measurements the input power exceeds the maximal input power of 1.41 [kW] given by Daikin.
I recorded the maximum at 1.8 [kW] though the hourly average never exceeds 1.5 [kW]. The power
counter which keeps overall min/max indicates short peaks up to 2.4 [kW].
Practical considerations
back to the content table
The noise of both internal and external unit is as low as announced by Daikin and definitely does not affect the comfort.
Note that the automatic fan speed control provides a good distribution of the heat and it appeared
unnecessary to set the fan speed manually.
It is worth to mention that the noise of the last generation fridge is significantly higher then that of the internal unit.
The warm air flow from the internal unit located close to the floor tends to "stick" to the floor and then diffuses gently upwards
resulting in the almost homogenous vertical temperature distribution.
The vertical temperature profile in the room measured at the location far from internal unit by calibrated infrared radiometer on a
homogenous vertical column exhibits peak-to-peak difference of 0.9 degree only, a rather dramatic improvement from 5 degree difference
with electrical convectors.
|

|
In the room with a low thermal capacity (internal insulation) where we installed the second unit, the effect of the heating is extraordinary fast.
After a cold night with open window when the starting temperature could be as low as 8 degrees, the 20 degree is reached after 10 minutes.
I should stress, that for me the drawbacks of the installation are close to negligible. I am listing them as a matter of information for those who
may be more concerned.
The humidification is almost useless at temperatures below 5 degrees which is confirmed by a carful reading of the
Daikin maintenance manual (page 22).
When used intensively, the internal unit requires almost every month cleaning of air filters. This rather a simple operation involves
nevertheless some cumbersome water rinsing and drying of big plastic filters.
Message to the author
since le March 16, 2008
|